440V 3-phase + Neutral Line Filters

1. Reduce the conducted interference from converter to electrical network.

2. Excellent insertion attenuation performance in the range of 150kHz-30MHz

3. Compact design, optimized industrial design

4. Installing this series of filters on the system incoming line can improve the reliability of the entire system

5. N99 series use copper bars, others use connectors


Product Details

Technical Specification

1. Rated Voltage: 440/250 VAC

2. Rated Frequency: 50Hz

3. Rated Current: 10 ~ 600A (@50℃)

4. High Voltage Test: P-E 2100VDC/2sec P-P 2100VDC/2sec

5. Temperature Range: -25 ~ +100℃

6. Design Standards: IEC/EN 60939, UL1283

7. Typical Work Frequency: 150kHz ~30MHz




Insertion Loss of Input Filter




Filter Selection Table

型號(hào)

額定電流

漏電流

能量損耗

端子類型

Type

Rated Current @40℃ (A)

Leakage Current@230VAC/50Hz
     (mA)

Power Loss @25℃/50Hz (W)

Terminal Block Type

RFI4NC8N06

8

<1

3.2

端子solid safety connector

RFI4NC16N06

16

<1

6.5

端子solid safety connector

RFI4NC25N10

25

<1

11.8

端子solid safety connector

RFI4NC36N10

36

<1

15.3

端子solid safety connector

RFI4NC50N16

50

<1

17.4

端子solid safety connector

RFI4NC65N16

65

<1

18.9

端子solid safety connector

RFI4NC100N35

100

<1

23.6

端子solid safety connector

RFI4NC130N50

130

<1

28.5

端子solid safety connector

RFI4NC160N95

160

<1

31

端子solid safety connector

RFI4NC200N95

200

<1

47.4

端子solid safety connector

RFI4NC300N99

300

<1

20.3

銅排 copper busbar

RFI4NC400N99

400

<1

36

銅排 copper busbar

RFI4NC600N99

600

<1

64.8

銅排 copper busbar

Product Applications

This series of filters are mainly used in industrial equipment, machinery, machine tools and diverse process automation systems with three-phase and neutral electricity supply. Due to the outstanding attenuation performance, this series of filters is also the first choice for noisy power supplies, and is used in renewable energy applications, high-power office equipment and other three-phase and neutral devices. Because of the relatively low leakage current. The series may even be used for some medical devices.


Product Dimensions


代號(hào) Code

電流
       Current (A)

A
   (mm)

B
   (mm)

C
   (mm)

D
   (mm)

E
   (mm)

F
   (mm)

G
   (mm)

H
   (mm)

U
   (mm)

V
   (mm)

W
   (mm)

X
   (mm)

Y1
   (mm)

Y2
   (mm)

Z
   (mm)

8-16

160

180

15.5

80

65

100

5.5

M5

 

 

 

 

 

 

 

25-36

160

180

35

100

75

115

5.5

M5

 

 

 

 

 

 

 

50-65

190

210

35

110

90

125

6.4

M6

 

 

 

 

 

 

 

100

230

120

38.5

125

150

163

6.4

M8

 

 

 

 

 

 

 

130

250

200

43

140

157

170

6.4

M8

 

 

 

 

 

 

 

160-200

280

220

52

170

166

180

6.4

M8

 

 

 

 

 

 

 

300

325

240

58

150

195

220

11

M10

120

4

25

12.5

72

43

11

400

325

240

58

150

195

220

11

M10

120

6

25

12.5

72

43

11

600

325

240

58

150

195

220

11

M10

120

8

25

12.5

72

43

11




Wire and Torque Selection for Input/Output Connector


-N6

-N10

-N16

-N35

-N50

-N95

多股軟線/mm2
     Litz Wire

0.5-6

0.5-10

1-16

10-35

16-50

25-95

美標(biāo)線規(guī)
     AWG Number

AWG8-26

AWG6-24

AWG4-20

AWG2-8

AWG6-1/0

AWG4-4/0

推薦扭矩/N.m
     Recommended Torque

1.36

1.36

2.71

4.41

4.41

19.2